Range Hood CFM: How Much Airflow a Gas or Electric Range Needs

Seven sizing rules checked against 92 ENERGY STAR certified hoods, two state codes and new field data on how often hoods actually run.
Primary data
ENERGY STAR Certified Ventilating Fans (range hoods)
Data period
Listings as of 2026-11-13
Latest release used
2026-11-13
Next release
Updated continuously by EPA
Geography
United States (with California and Washington code tables)
Sources
16 (12 Tier 1)
Short answer

None of the 92 ENERGY STAR range hoods listed on 2026-11-15 exceeds 210 CFM, so no certified model reaches the 400 CFM make-up air trigger. Range hood CFM rules split by fuel: California asks 110 to 160 CFM over electric and 180 to 280 over gas, while HVI advises 100 CFM per foot of wall range.

0 of 92ENERGY STAR range hoods above 400 CFM (0.0%), the IRC make-up air trigger[1][14]
210 CFMHighest working-speed airflow of any certified range hood; median 150 CFM[1]
16.3%Certified hoods meeting California's 180 CFM gas minimum for homes over 1,500 sq ft[1][4]
23.8%Cooking events with the hood on in a 2026 LBNL field study[7]

No ENERGY STAR range hood is rated above 210 CFM, and none reaches 400

The brief planned three airflow classes for certified hoods. The data fills only the first one: all 92 listings sit between 120 and 210 CFM.

We pulled every range hood row from the ENERGY STAR Certified Ventilating Fans dataset on 2026-11-15. EPA last updated the list on 2026-11-13. There are 92 range hood listings among 1,145 certified ventilating fans.

The highest working-speed airflow on the list is 210 CFM. The median is 150 CFM and the lowest is 120 CFM. 0 listings fall in the 301 to 400 CFM class and 0 in the over-400 class, so the share of certified hoods above the IRC make-up air trigger is 0.0%.

Certified range hoods by working-speed airflow

ENERGY STAR listings, 2026-11-15

Certified range hoods by working-speed airflowBar chart of 92 ENERGY STAR range hood listings by working-speed airflow: 41 listings at 150 CFM, 13 at 120 CFM, 12 at 160 CFM, and the highest is 210 CFM with 2 listings. None is above 210 CFM.listings120 CFM13.0122 CFM1130 CFM6132 CFM1139 CFM1141 CFM1150 CFM41.0160 CFM12.0170 CFM1180 CFM3190 CFM2200 CFM8210 CFM2

Source: U.S. EPA ENERGY STAR Certified Ventilating Fans dataset, range hoods, pulled 2026-11-15

The ceiling is built into the label. The ENERGY STAR key product criteria define the range hood category as hoods of 75 W or less, with at least 2.8 CFM per watt. At exactly 75 W and 2.8 CFM per watt a hood moves 210 CFM, the same figure as the top listing. A more efficient hood could move more air inside 75 W, but none on the list does.

ENERGY STAR range hoods by airflow class, 2026-11-15 Download CSV
Airflow classListingsShare of listings (%)Median CFMMedian sonesMedian CFM per watt
Up to 300 CFM92100.0150.01.54.6
301 to 400 CFM00.0None listedNone listedNone listed
Over 400 CFM00.0None listedNone listedNone listed

Airflow is the working-speed rating ENERGY STAR publishes for range hoods. 92 listings; 5 have no sone value.

Source: [1] U.S. EPA ENERGY STAR

Listings repeat. The 92 rows reduce to 30 distinct performance configurations from 6 partners and 8 brands, likely because one design is listed separately for each finish or width. 41 of the 92 listings were first certified in 2025.

Range hood listings by year certified

ENERGY STAR, 2026 through 2026-11-13

Range hood listings by year certifiedColumn chart of range hood listings by year first certified: 41 of 92 listings were certified in 2025, 17 in 2024 and 4 so far in 2026.010.020.030.040.050.0listings5201962020720212202210.0202317.0202441.0202542026

Source: ENERGY STAR Certified Ventilating Fans dataset, date_qualified field

Seven range hood CFM rules, side by side, for gas and electric

For one 36-inch range, the rules in circulation ask for anything from 110 CFM to 600 CFM. Only the state codes are binding, and they sit at the low end.

Range hood CFM rules side by side Download CSV
RuleWho sets itStatusHood over electric rangeHood over gas range
100 CFM per 10,000 BTURetailer guidance (Proline)Rule of thumbWidth in inches x 10100 CFM per 10,000 BTU
100 CFM per linear foot (wall), 150 (island)Home Ventilating InstituteTrade guidance100 CFM per foot; minimum 40Same; manufacturer advice for pro-style
Title 24 Table 150.0-G, homes over 1,500 sq ftCalifornia Energy CommissionState code, new homes110 CFM or 50% CE180 CFM or 70% CE
Title 24 Table 150.0-G, homes under 750 sq ftCalifornia Energy CommissionState code, new homes160 CFM or 65% CE280 CFM or 85% CE
WAC Table M1505.4.4.3Washington StateState code160 CFM or 65% CE250 CFM or 80% CE
IRC 2021 make-up air triggerInternational Code CouncilModel code, where adoptedAbove 400 CFM, only with a vented fuel applianceAbove 400 CFM, only with a vented fuel appliance
ENERGY STAR range hood categoryU.S. EPAVoluntary label75 W or less, 2.8 CFM per watt, 2.0 sones75 W or less, 2.8 CFM per watt, 2.0 sones

CE = capture efficiency rated to ASTM E3087. Title 24 and Washington accept either the airflow or the CE rating. The 100 CFM per 10,000 BTU rule has no code or standards-body source that we could open.

Source: [16][13][4][6][14][2] Proline Range Hoods (retailer); Home Ventilating Institute (HVI); California Energy Commission; Washington State Legislature; Energy Vanguard; U.S. EPA ENERGY STAR

The 100 CFM per 10,000 BTU rule for gas is the one most buying guides repeat. We found it published by a hood retailer, Proline Range Hoods, which also recommends at least 600 CFM for most kitchens. We could not find it in any code or standards document we opened, so it is shown as a rule of thumb.

The Home Ventilating Institute sizes by width instead: 100 CFM per linear foot for a range against a wall and 150 CFM per foot over an island. Its table gives 250 CFM for a 30-inch wall hood, 300 CFM for 36 inches and 400 CFM for 48 inches, with minimums of 100, 120 and 160 CFM.

CFM each rule asks for

Single values; code rows use the airflow path

CFM each rule asks forHorizontal bar chart comparing airflow asked for by each rule: California Title 24 asks 110 CFM over an electric range in a home over 1,500 sq ft and 180 CFM over gas; Washington asks 160 and 250; HVI recommends 300 CFM for a 36-inch wall hood and 450 for a 36-inch island; a retailer recommends 600. The highest ENERGY STAR certified hood is 210 CFM.CFMT24 electric, big home110HVI 36in wall minimum120ES certified median150WA electric range160T24 gas, big home180ES certified maximum210WA gas range250T24 gas, small home280HVI 36in wall advice300BTU rule, 40k BTU400HVI 36in island450Retailer advice600

Sources: CEC Table 150.0-G; WAC 51-51-1505; HVI; ENERGY STAR; Proline. BTU rule row is our calculation.

The gap between advice and code is wide. HVI's 36-inch wall recommendation of 300 CFM is 120 CFM above California's 180 CFM gas minimum for a home over 1,500 sq ft. ASHRAE's residential ventilation standard is the base for both state tables, but its text is sold, not free, so we cite the state versions that adopt it with amendments.

The 400 CFM make-up air trigger depends on what else burns in the house

The IRC make-up air rule is not a plain 400 CFM cap. Since the 2018 edition it applies only when an atmospherically vented fuel appliance shares the home's air.

As quoted by Energy Vanguard, the 2021 IRC requires make-up air for each exhaust system capable of more than 400 CFM where a gas, liquid or solid fuel-burning appliance that is neither direct-vent nor mechanical draft is inside the dwelling's air barrier. The make-up air must roughly equal the exhaust rate.

Fine Homebuilding traces the 400 CFM rule to the 2009 IRC, where it applied to every large hood. The 2018 edition narrowed it to homes with naturally drafted appliances, and the 2021 edition kept that wording. The ICC's own code page blocks automated access, so we did not open it directly; both secondary sources agree on the wording.

Where each sizing rule crosses the 400 CFM make-up air trigger Download CSV
RuleCrossing pointBasis
100 CFM per 10,000 BTU (gas)40,000 BTU per hour total400 / 100 x 10,000
HVI wall rate, 100 CFM per foot48-inch hood (400 CFM)HVI width table
HVI island rate, 150 CFM per footAbout 32 inches wide400 / 150 = 2.67 ft
Retailer recommendation, 600 CFMAbove the trigger600 > 400
Highest ENERGY STAR hood, 210 CFMBelow the trigger210 < 400

The trigger applies only where a fuel-burning appliance that is neither direct-vent nor mechanical draft sits inside the air barrier (2021 IRC as quoted by Energy Vanguard).

Source: [16][13][14][1] Proline Range Hoods (retailer); Home Ventilating Institute (HVI); Energy Vanguard; U.S. EPA ENERGY STAR

Each sizing rule crosses the trigger at a different point. Under the BTU rule, a cooktop totaling more than 40,000 BTU per hour calls for a hood above 400 CFM. Under HVI's island rate, any island hood wider than about 32 inches does. No ENERGY STAR certified hood comes close.

Gas water heater with a metal vent pipe in a utility closet
Illustrative photograph. Generated image, not a specific project.

Certified hoods run at a median 1.5 sones and 4.6 CFM per watt

Within the narrow certified band, quieter and more efficient hoods are concentrated in a small set of configurations.

Across listings with a sound rating, the median certified hood is rated 1.5 sones and the loudest 2.0 sones, the ENERGY STAR limit. 55.2% are 1.5 sones or quieter. 5 listings report no sone value.

Median efficacy is 4.6 CFM per watt, 1.64 times the 2.8 CFM per watt floor. Dividing listed airflow by efficacy gives a median fan power of 32.6 W, and no listing tops 58.3 W.

Certified range hoods within the 120 to 210 CFM band Download CSV
Working-speed bandListingsMedian CFMMedian sonesMedian CFM per wattMedian fan watts
100 to 130 CFM20120.01.54.231.0
131 to 160 CFM56150.02.04.632.6
161 to 210 CFM16200.00.115.412.3

Fan watts = airflow / efficacy. 11 of the 16 listings in the top band report 0.0 or 0.1 sones and 14.2 to 16.6 CFM per watt, all from one partner.

Source: [1] U.S. EPA ENERGY STAR

ENERGY STAR data cannot answer how loud a 600 CFM hood is, because no certified hood is that large. Washington caps intermittent kitchen exhaust at 3 sones at an airflow setting of 100 CFM or more. That limit applies at the rated setting, not at boost speed.

California and Washington ask more CFM over gas, or a capture efficiency score

Both state codes set fuel-specific minimums and let a hood comply by tested capture efficiency instead of airflow.

California's 2025 single-family compliance form reproduces Table 150.0-G. A hood over an electric range needs 110 CFM in homes over 1,000 sq ft, 130 CFM at 750 to 1,000 sq ft and 160 CFM below 750 sq ft. Over a gas range it needs 180, 250 or 280 CFM by the same size bands.

Title 24 airflow minimums and how many certified hoods meet them Download CSV
Home floor areaElectric range minimum (CFM)Certified hoods meeting it (%)Gas range minimum (CFM)Certified hoods meeting it (%)
Over 1,500 sq ft110100.018016.3
Over 1,000 to 1,500 sq ft110100.02500.0
750 to 1,000 sq ft13084.82800.0
Under 750 sq ft16030.42800.0

Minimums from Table 150.0-G (2025 Standards). Share = ENERGY STAR range hood listings whose working-speed airflow is at or above the minimum. Hoods can also comply by capture efficiency, which ENERGY STAR does not list.

Source: [4][1] California Energy Commission; U.S. EPA ENERGY STAR

Certified hoods meeting each airflow minimum

Share of 92 ENERGY STAR range hood listings

Certified hoods meeting each airflow minimumColumn chart: 100 percent of certified range hoods meet 110 CFM, 84.8 percent meet 130 CFM, 30.4 percent meet 160 CFM, 16.3 percent meet 180 CFM, and 0 percent meet 250 or 280 CFM, the gas minimums for smaller California homes.025.050.075.0100125%100110 CFM84.8130 CFM30.4160 CFM16.3180 CFM0250 CFM0280 CFM

Source: ENERGY STAR range hood listings 2026-11-15; minimums from Title 24 Table 150.0-G and WAC 51-51-1505

Matched against those minimums, 100.0% of certified hoods meet the 110 CFM electric figure, 16.3% meet the 180 CFM gas figure for the largest homes and 0.0% meet 250 or 280 CFM. A certified hood can still comply in a small California home by its capture efficiency rating, which ENERGY STAR does not publish.

Washington's amendments use one row for all home sizes: 160 CFM or 65% capture efficiency over electric, 250 CFM or 80% over combustion ranges, and 300 CFM for downdraft and other kitchen fans. California sets the same 300 CFM for downdraft and a continuous option of 5 air changes per hour for an enclosed kitchen. 30.4% of certified hoods meet Washington's electric figure by airflow.

Under-cabinet range hood above an induction cooktop in a small kitchen
Illustrative photograph. Generated image, not a specific project.

Field studies find the hood switched on in about one cooking event in four

Airflow on paper matters less if the fan stays off. New LBNL field data put hood use at 23.8% of cooking events.

The CEVICA study, led with Lawrence Berkeley National Laboratory, logged 4,184 cooking events and 1,038 hood use events in 40 San Joaquin Valley homes. In the Phase 1 sample, hoods ran for 3 minutes or more in 23.8% of cooking events: 26.9% with gas and 20.4% with induction.

Range hood use during cooking

CEVICA homes, share of events with hood on 3+ min

Range hood use during cookingGrouped column chart: hoods were on in 26.9 percent of gas cooking events and 20.4 percent of induction cooking events; use rose to 35.0 and 38.1 percent when cooking produced particles.010.020.030.040.050.0%35.038.1Particle events23.613.1No particles26.920.4All cookingGas stoveInduction stove

Source: Fang et al. 2026, LBNL, IAQVEC 2026 paper 514, Table 1

How often range hoods were switched on during cooking, CEVICA study Download CSV
Cooking eventsGas stove (%)Induction stove (%)All stoves (%)
With particle emissions35.038.135.2
Without particle emissions23.613.118.1
All cooking26.920.423.8

Phase 1, cohort 1, 1,543 cooking events in San Joaquin Valley homes. Use = hood on for 3 minutes or more.

Source: [7] Lawrence Berkeley National Laboratory via OSTI

Use rose when cooking produced particles: 35.0% of those gas events and 38.1% of induction events. With gas cooking, NO2 added per minute of cooking was 30% lower when the hood ran, and integrated NO2 was about 45% higher in events without hood use. The same team measured time-integrated NO2 14.2 ppb lower with electric cooking; the stove comparison is covered in our induction vs gas stove report.

An earlier simulation by Logue and colleagues estimated that 62%, 9% and 53% of occupants in Southern California homes cooking with gas and no hood use exceed acute standards for NO2, CO and formaldehyde. It modeled hood use with the 55% mean capture efficiency measured in California homes. The EPA lists an exhaust fan vented outdoors over gas stoves among its steps to reduce NO2 exposure.

Federal surveys do not record whether homes have a vented hood

No national count of vented range hoods exists in the main federal housing energy survey.

We searched the EIA RECS 2020 and RECS 2024 codebooks for hood, exhaust and vent variables. Neither has a range hood or kitchen exhaust question; the only exhaust item is an attic fan. That means no federal figure shows how many U.S. kitchens have a hood or whether it vents outside.

For bathroom fans, see our bathroom exhaust fan CFM report. State and local rules on gas appliances are tracked in the gas stove ban tracker. Hood installation usually falls late in a remodel; our kitchen remodel timeline shows where.

Ratios behind the comparison

Share of ENERGY STAR range hood listings above the 400 CFM make-up air trigger

Formulalistings above 400 CFM / all listings x 100

Inputs: rows 17, 1 (fact sheet rows)

Result: 0.0% (0 of 92 listings)

No ENERGY STAR certified hood can trigger IRC make-up air at its rated working speed. Buyers sizing above 400 CFM are choosing outside the certified pool.

Limitations: Working-speed airflow; a hood can have a higher boost speed

Airflow at the ENERGY STAR range hood ceiling of 75 W and the 2.8 CFM per watt floor

Formula75 x 2.8

Inputs: rows 22, 23 (fact sheet rows)

Result: 210 CFM

The 75 W category limit and 2.8 CFM per watt floor together point to 210 CFM, matching the highest listing.

Limitations: A more efficient hood can move more air within 75 W

Gas burner input matched by the highest-airflow certified hood under the 100 CFM per 10,000 BTU rule

Formula210 CFM / 100 x 10,000

Inputs: rows 7, 53 (fact sheet rows)

Result: 21,000 BTU per hour

By the BTU rule, the largest certified hood suits a cooktop with total burner input of 21,000 BTU per hour; the median suits 15,000.

Limitations: Rule of thumb from a retailer, not a code

Total cooktop input at which the BTU rule crosses the 400 CFM trigger

Formula400 / 100 x 10,000

Inputs: rows 51, 53 (fact sheet rows)

Result: 40,000 BTU per hour

Above this total cooktop input, the BTU rule asks for more than 400 CFM.

Limitations: Trigger also needs an atmospherically vented appliance

Island hood width at which the HVI recommended rate crosses 400 CFM

Formula400 / 150 CFM per foot = 2.67 ft x 12

Inputs: rows 51, 45 (fact sheet rows)

Result: 32 inches

Island hoods wider than about 32 inches at HVI's recommended rate pass 400 CFM.

Limitations: Rounded to the inch; 2.67 ft

Share of certified hoods meeting Title 24 airflow for gas, homes over 1,500 sq ft (180 CFM)

Formulalistings >= 180 CFM / 92 x 100

Inputs: rows 27, 1 (fact sheet rows)

Result: 16.3%

Most certified hoods fall short of California's gas airflow minimum even for the largest homes, unless they comply by capture efficiency.

Limitations: Working-speed rating vs code rating point may differ

Median fan power of certified range hoods

Formulamedian of (airflow / efficacy) per listing

Inputs: rows 8, 12 (fact sheet rows)

Result: 32.6 W

Certified hoods draw well under half the 75 W category limit at listed airflow.

Limitations: Computed from listed fields, not measured

Share of CEVICA cooking events without range hood use

Formula100 - 23.8

Inputs: row 58 (fact sheet rows)

Result: 76.2%

In the CEVICA homes, about three in four cooking events happened with the hood off or on for under 3 minutes.

Limitations: One California cohort

Download the calculations (CSV)

Where the numbers diverge

  1. ENERGY STAR listed 92 certified range hoods as of its 2026-11-13 update, out of 1,145 certified ventilating fans of all types (8.0%).[1]
  2. Working-speed airflow of certified range hoods ranges from 120 to 210 CFM, with a median of 150 CFM (United States and Canada listings, 2026).[1]
  3. 0 of 92 certified range hoods (0.0%) is rated above 400 CFM, and 0 is rated between 301 and 400 CFM.[1]
  4. The 92 listings collapse to 30 distinct performance configurations from 6 ENERGY STAR partners and 8 brands.[1]
  5. ENERGY STAR range hood criteria cover hoods of 75 W or less and require at least 2.8 CFM per watt and no more than 2.0 sones (Version 4.1).[2]
  6. The median certified hood uses 32.6 W of fan power at its listed airflow and the highest uses 58.3 W (our calculation from listed airflow and efficacy).[1]
  7. 55.2% of certified hoods with a sound rating are rated 1.5 sones or quieter; the loudest is 2.0 sones.[1]
  8. California's 2025 Title 24 Table 150.0-G sets 110 to 160 CFM over electric ranges and 180 to 280 CFM over gas ranges, scaled up as homes get smaller.[4]
  9. Washington requires 160 CFM over electric and 250 CFM over combustion ranges, or 65% and 80% capture efficiency (effective 2024-03-16).[6]
  10. HVI recommends 100 CFM per linear foot for wall ranges and 150 CFM for islands, with minimums of 40 and 50 CFM per foot.[13]
  11. Under the 2021 IRC, exhaust above 400 CFM needs make-up air only where a fuel-burning appliance that is neither direct-vent nor mechanical draft is inside the air barrier.[14][15]
  12. In the CEVICA study, range hoods ran during 26.9% of gas cooking events and 20.4% of induction cooking events (California, 2026 publication).[7]
  13. A 2014 simulation estimated that 62% of Southern California occupants in homes cooking with gas and no hood use exceed acute NO2 standards.[9]

Summary

  • ENERGY STAR lists 92 certified range hoods (2026-11-15); every one is rated at or below 210 CFM at working speed, and 0.0% exceed the 400 CFM make-up air trigger.
  • The ENERGY STAR range hood category only covers hoods of 75 W or less, and 75 W at the 2.8 CFM per watt floor works out to 210 CFM, the same as the top listing.
  • Certified hoods run at a median 150 CFM, 1.5 sones and 4.6 CFM per watt; no range hood is on the 2026 Most Efficient list.
  • Code minimums are far below rule-of-thumb sizes: California asks 180 CFM over a gas range in homes over 1,500 sq ft, HVI recommends 300 CFM for a 36-inch wall hood and a retailer recommends 600.
  • Only 16.3% of certified hoods meet California's 180 CFM gas minimum by airflow, and 0.0% meet the 250 to 280 CFM gas minimums for smaller homes.
  • The 2021 IRC make-up air rule applies above 400 CFM only when a fuel-burning appliance that is neither direct-vent nor mechanical draft sits inside the air barrier.
  • In 40 California homes studied by LBNL, hoods ran in 23.8% of cooking events, and NO2 added per minute of gas cooking was 30% lower when they did.

Questions people ask

Is 300 CFM enough for a gas range?

300 CFM exceeds every state code minimum we found: California asks 180 to 280 CFM over gas and Washington 250 CFM. It matches HVI's recommendation for a 36-inch wall hood. Under the 100 CFM per 10,000 BTU rule of thumb, 300 CFM fits a cooktop up to 30,000 BTU per hour.

Do I need make-up air for a range hood?

Under the 2021 IRC, only if the hood can exhaust more than 400 CFM and a fuel-burning appliance that is neither direct-vent nor mechanical draft is inside the air barrier. An all-electric home with a large hood does not trigger it. Local amendments can differ.

Do recirculating hoods work?

HVI states that nonducted, recirculating hoods provide no actual ventilation. Washington allows listed ductless hoods only where an enclosed kitchen also has continuous exhaust to code rates.

How loud is a 600 CFM hood?

Certified data cannot say: no ENERGY STAR hood is above 210 CFM. Certified hoods are rated at a median 1.5 sones. Washington limits intermittent kitchen exhaust to 3 sones at a setting of 100 CFM or more, which says nothing about boost speeds.

For journalists and researchers

If you cite only a few, cite these

  1. 0 of 92 ENERGY STAR range hoods exceed 400 CFM; the highest is 210 CFM (2026-11-15).[1]
  2. California Title 24 Table 150.0-G: 110 to 160 CFM over electric, 180 to 280 CFM over gas.[4]
  3. Hoods ran in 23.8% of cooking events in CEVICA homes (LBNL, 2026).[7]

Most quotable statistics

  • None of the 92 ENERGY STAR certified range hoods listed on 2026-11-15 is rated above 210 CFM; 0.0% exceed the 400 CFM IRC make-up air trigger.[1][14]
  • Only 16.3% of ENERGY STAR range hoods meet California's 180 CFM gas minimum for homes over 1,500 sq ft by airflow alone.[1][4]
  • California's 2025 Title 24 asks 110 to 160 CFM over electric ranges and 180 to 280 CFM over gas ranges.[4]
  • Range hoods ran in 23.8% of cooking events across 40 California homes in a 2026 LBNL field study.[7]
  • HVI recommends 300 CFM for a 36-inch wall hood, 120 CFM above California's gas minimum for large homes.[13][4]
  • Under the 100 CFM per 10,000 BTU rule of thumb, any cooktop above 40,000 BTU per hour needs a hood above 400 CFM.[16][14]

Press summary

Kitchen and Bath Renovators compared the main range hood sizing rules with federal certification data. Of 92 ENERGY STAR certified range hoods listed on 2026-11-15, none is rated above 210 CFM at working speed, and none reaches the 400 CFM level at which the 2021 International Residential Code can require make-up air. The ENERGY STAR range hood category is limited to hoods of 75 W or less, which caps airflow near 210 CFM at the minimum efficacy. State codes ask for far less than common buying advice: California's 2025 Title 24 sets 110 to 160 CFM over electric ranges and 180 to 280 CFM over gas, while Washington sets 160 and 250. HVI recommends 300 CFM for a 36-inch wall hood and a retailer suggests 600. Only 16.3% of certified hoods meet California's 180 CFM gas minimum by airflow. A 2026 LBNL field study found hoods ran in 23.8% of cooking events.

Suggested headlines

  • No ENERGY STAR range hood tops 210 CFM, far below the 400 CFM make-up air line
  • Range hood CFM rules run from 110 to 600 CFM for the same 36-inch range
  • California asks 180 to 280 CFM over gas; only 16.3% of certified hoods qualify by airflow
  • Hoods ran in fewer than one in four cooking events in an LBNL field study
  • The 400 CFM make-up air rule only bites in homes with naturally vented gas appliances

How to cite this report

Kitchen and Bath Renovators. (2026). Range Hood CFM: How Much Airflow a Gas or Electric Range Needs. Retrieved from https://kitchenandbathrenovators.com/research/range-hood-cfm/

Reuse license

Data and tables are licensed CC BY 4.0. Attribution: “Source: Kitchen and Bath Renovators, Range Hood CFM: How Much Airflow a Gas or Electric Range Needs” with a link to this page.

Download the data

Every table in this report is available as a CSV under CC BY 4.0. The fact sheet lists each value with its source URL and access date.

Frequently asked questions

How many CFM does a range hood need for an electric range?

California's Title 24 asks 110 CFM in homes over 1,000 sq ft, rising to 160 CFM under 750 sq ft. Washington asks 160 CFM. HVI recommends 100 CFM per linear foot against a wall.

How many CFM does a range hood need for a gas range?

California asks 180 CFM in homes over 1,500 sq ft and 250 to 280 CFM in smaller homes; Washington asks 250 CFM. A retailer rule of thumb is 100 CFM per 10,000 BTU.

Does induction need less range hood CFM than gas?

Both state codes treat induction as electric, so the minimum is lower: 110 to 160 CFM in California versus 180 to 280 CFM for gas. Cooking itself still makes particles; in CEVICA, hood use was 38.1% for particle-producing induction events.

What is the most CFM an ENERGY STAR range hood has?

210 CFM at working speed, from the list updated 2026-11-13. The median is 150 CFM across 92 listings.

Why are ENERGY STAR range hoods so small?

The ENERGY STAR range hood category covers hoods of 75 W or less with at least 2.8 CFM per watt. At those limits a hood moves 210 CFM.

What is capture efficiency?

Capture efficiency is the share of cooking pollutants a hood removes directly, rated under ASTM E3087. California and Washington accept it in place of airflow, for example 70% CE instead of 180 CFM over gas in large California homes.

When did the 400 CFM make-up air rule start?

Fine Homebuilding dates it to the 2009 IRC. The 2018 edition limited it to homes with naturally drafted fuel appliances inside the envelope, and the 2021 edition kept that.

How often do people actually use their range hood?

In 40 California homes, hoods ran for 3 minutes or more in 23.8% of cooking events, per a 2026 LBNL study.

Does using the hood reduce NO2 from a gas stove?

In CEVICA, NO2 added per minute of gas cooking was 30% lower with the hood on. A 2014 simulation assumed 55% capture efficiency for hoods in California homes.

What sone rating is quiet for a range hood?

ENERGY STAR caps certified hoods at 2.0 sones; 55.2% of certified hoods are rated 1.5 sones or quieter. Washington allows up to 3 sones for intermittent kitchen exhaust.

Reproduce this analysis

Every figure comes from the files below. The scripts that pulled and computed them are kept with the report and can be re-run.

DatasetPublisherSourceQuery or filterRows usedRetrieved
ENERGY STAR Certified Ventilating FansU.S. EPA ENERGY STARFile or endpoint$where=unit_type='Range Hood'&$limit=5000; full table also pulled for the 1,145 total92 range hood rows of 1,1452026-11-15
ENERGY STAR Most Efficient Ventilating FansU.S. EPA ENERGY STARFile or endpoint$select=unit_type,count(*)&$group=unit_type2 groups, 0 range hoods2026-11-15
CF2R-MCH-32-H, 2025 Single-Family, Tables 150.0-E to 150.0-GCalifornia Energy CommissionFile or endpointTable 150.0-G read from PDF4 floor-area rows x 2 fuels2026-11-15
WAC 51-51-1505Washington State LegislatureFile or endpointTables M1505.4.4.1 and M1505.4.4.3, M1505.4.4.2 sound limits2 fuel rows2026-11-15
RECS 2020 and 2024 codebooks (shared copies)U.S. Energy Information AdministrationFile or endpointKeyword search hood, exhaust, vent in build/kitchenandbathrenovators.com/research_shared/recs2020/ and recs2024/ codebooks0 matching variables2026-11-15

Data quality and exclusions

  • 92 range hood rows kept; 0 dropped. 1,053 non-hood rows (bath, utility and in-line fans) excluded by the unit_type filter.
  • 5 listings have no sone value; they are excluded from sone medians and from the 1.5-sone share (base 87).
  • 11 listings from one partner report 0.0 or 0.1 sones with 14.2 to 16.6 CFM per watt; kept as published and flagged.
  • Multi-speed listings report up to three airflows; we used the highest, which is the listed working-speed rating.
  • The 92 listings contain 30 distinct performance configurations; counts and shares are by listing, as ENERGY STAR publishes them.

Methodology

Source selection: we used the ENERGY STAR Certified Ventilating Fans dataset as the primary data, code tables published by the California Energy Commission and the Washington State Legislature, peer-reviewed or laboratory research from LBNL and Environmental Health Perspectives, and HVI guidance. Retailer and trade-press pages are used only to show who publishes a rule or to quote code text we could not open at the ICC.

Inclusion: every row with unit_type equal to Range Hood on 2026-11-15 (92 rows). Airflow per listing is the highest of the up to three listed working-speed airflows; efficacy is the value paired with that airflow; sones is the upper end of the listed range.

Conflicts: where rules disagree we show them side by side rather than choosing one. The 100 CFM per 10,000 BTU rule is labeled a rule of thumb because no code or standards text we opened contains it.

Derived metrics: shares are listing counts over 92; fan watts are airflow divided by efficacy; BTU and width crossing points are arithmetic on the published rules. Formulas and input rows are in derived_metrics.csv; the pull and computation scripts are in scripts/.

Limitations: ENERGY STAR airflow is a working-speed rating; code compliance points and boost speeds can differ. CEVICA covers 40 homes in one California region. Last updated 2026-11-15.

This report presents published data with its limitations. It is not legal, financial or investment advice.